Micrometrix사의
Charles Veal이 발표한 "Application of Streaming Current Technology in Water
Treatment"는 SCD의 최적 Setpoint 설정방법에 대해 소개하고 있습니다. 아래에 일부 내용을 발췌하여 놓았습니다. 전체 내용을
보시기를 원하시는 분은 첨부한 화일을 다운로드하여 보시기 바랍니다.
- 일부 내용 발췌 - The Streaming
Current Meter provides a valuable tool for water treatment plant operators to
optimize and control coagulant dosage. A major advantage of the SCM is that it
provides information at the beginning of the process. This measurement
allows operators to know precisely if the coagulant dosage is at the optimum
point. Alarms and control systems can enhance the use of the SCM. It is
important that the instrument be installed and operated properly to receive the
maximum benefit. The SCM is an online instrument that continuously samples
the treated water just after coagulant is added. Chemical coagulants are added
to surface water to destabilize the colloids and suspended material and
promote flocculation. In raw untreated water, colloidal particles are stabilized
with electrostatic forces. Oppositely charged chemicals reduce these repulsive
forces to allow the particles to agglomerate or floc. The floc is then settled
or filtered. The SCM measures how well the chemicals are doing their job by
detecting the residual charge in the sample. The measurement indicates if the
surface charges have been neutralized. So anything that will affect the charge
balance will affect the SCM reading. |